Spares / Spares by Brand / DSE Deep Sea Electronics / DSE Generator Control Modules
| 1+ | $2,607.00 |
| 2+ | $2,343.00 |
The DSE8660 MKII is the latest and most advanced Auto Transfer Switch & Mains (Utility) Control Module within the DSE synchronising and load sharing control module range. Developed alongside the DSE8610 MKII this control module provides industry-leading features and benefits for the most complex grid type generator installations.
| Specifications | |
|---|---|
| DC SUPPLY | |
Continuous Voltage Rating | 8 V to 35 V Continuous |
| Cranking Dropouts | Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. |
| Maximum Operating Current | 460 mA at 12 V, 245 mA at 24 V |
| Maximum Standby Current | 375 mA at 12 V, 200 mA at 24 V |
| Charge Fail/Excitation Range | 0 V to 35 V |
| OUTPUTS | |
| Output A (Fuel) | 15 A DC at supply voltage |
| Output B (Start) | 15 A DC at supply voltage |
| Outputs C & D | 8 A AC at 250 V AC (Volt free) |
| Auxiliary Outputs E, F, G, H, I & J | 2 A DC at supply voltage |
| GENERATOR & BUS | |
| Voltage Range | 15 V to 333 V AC (L-N) |
| Frequency Range | 3.5 Hz to 75 Hz |
| MAGNETIC PICK UP | |
| Voltage Range | +/- 0.5 V to 70 V |
| Frequency Range | 10,000 Hz (max) |
| Minimum Load Impedance | 1000Ω Fully isolated |
| Gain Voltage | 0 V to 10 V DC Fully isolated |
| Offset Voltage | +/- 10 V DC Fully isolated |
| BUILT IN AVR CONTROL | |
| Minimum Load Impedance | 1000Ω Fully isolated |
| Gain Voltage | 0 V to 10 V DC Fully isolated |
| Offset Voltage | +/- 10 V DC Fully isolated |